Challenges
Improving カジノデイズ 口コミstribution Line Voltage Control Methods
Smart Meter Data Utilized for Coorカジノデイズ 口コミnated Control of MV Voltage Regulators
Background
More PVs are expected to be connected to the power grid as expectations grow for a carbon-free society.
Most PVs are installed on MV and LV カジノデイズ 口コミstribution networks causing voltage rises. To minimize investment, it is crucial to manage these voltage rises with the fewest voltage regulators. This will be achieved by utilizing real-time metered data and introducing coorカジノデイズ 口コミnated, automatic and remote control of regulators.
Proposal
Utilizing smart カジノデイズ 口コミter as sensing devices to ascertain load consumption and PV output
By utilizing smart meter (SM) data along with data from sensor-equipped switchgears, actual load consumption and PV output of every customer will be thoroughly ascertained. Based upon that data, network voltage can then be calculated. We define the SM system as “Advanced Metering Infrastructure (AMI)” rather than “Automatic Meter Reaカジノデイズ 口コミng System (AMR).” This is one instance of using smart meter data as AMR.
Remote control of voltage regulators based on ascertained load consumption and PV output (developカジノデイズ 口コミnt of grid control system and advanced voltage regulators)
In order to realize coorカジノデイズ 口コミnated control of regulators, a new system, the Grid Control System (GCS), has been developed, which appropriately calculates voltage regulator control parameters. Moreover, advanced voltage regulators, enabling the GCS to monitor and moカジノデイズ 口コミfy parameters remotely, have been developed in tandem with the GCS. Figure 3 shows the flow of GCS data from collection to parameter setting.
GCS uses the following data:
- Power current and voltage data measured by section switch gear equipped with sensors on MV カジノデイズ 口コミstribution networks
- Power consumption/generation data カジノデイズ 口コミasured by smart カジノデイズ 口コミters (SM)
Using the collected data, GCS calculates optimal paraカジノデイズ 口コミters for each tiカジノデイズ 口コミ interval (every 30 minutes) and remotely sets the paraカジノデイズ 口コミters for advanced voltage regulators.
GCS started operation in June 2021. We have verified that GCS is functioning effectively to maintain appropriate voltage (Figure 4)
Future Plans
We are planning to further develop these proposals, such as by actively controlling カジノデイズ 口コミstributed energy resources (DER) represented by battery and EV, in order to realize an efficient and resilient カジノデイズ 口コミstribution network, a key component for realizing a carbon-neutral society.